HY5W-9L 9 kV Metal-oxide Surge Arrester

Product Overview
PRODUCT OVERVIEW

HY5W-9L 9kV polymer-housed metal-oxide surge arrester for overvoltage protection of 10kV/11kV distribution systems.

Brand:Gaosuo Electric Co., Ltd.
Origin:China
Material:Quality Steel
After-sales:1-Year Warranty
  • Features
  • HY5W-9L 9 kV Metal-oxide Surge Arrester

    General information on surge arresters (applicable to all models of this series)

    The core element of a metal-oxide surge arrester (MOA) is the metal-oxide varistor (MOV), which has non-linear V-I characteristics: no delay to steep-front voltage, low switching residual voltage and no discharge dispersion, so that the protection margins against lightning waves, switching waves and steep-front waves are nearly identical, and it can absorb lightning overvoltage, switching overvoltage and power-frequency temporary overvoltage.

    This polymer-housed series is formed by one-piece silicone-rubber moulding, with good sealing, high explosion-proof performance, pollution resistance without cleaning, resistance to electrical erosion and ageing, small size and light weight, and is easy to install and maintain.

    Manufacturing standards: GB11032-2000 (eqv IEC 60099-4:1991) Metal-oxide surge arresters without gaps for AC systems; JB/T 8952-2005 Polymer-housed metal-oxide surge arresters without gaps for AC systems.

    V-I characteristic curve

    V-I characteristic curve of the metal-oxide surge arrester

    Complete type designation

    complete type designation of the metal-oxide surge arrester

    Product Overview

    The HY5W-9L polymer-housed metal-oxide surge arrester is designed for 10 kV distribution networks and pole-mounted distribution transformers, with metal-oxide varistors (MOV) as the core element. It features fast steep-front response, good non-linear V-I characteristics and high current-carrying capacity, effectively limiting the overvoltage amplitude and protecting pole-mounted transformers, distribution lines and distribution cabinets against lightning impulse and switching overvoltages. The product has passed the type tests of the national quality supervision and test centre for insulators and surge arresters, and its parameters comply with international standard IEC 60099-4.

    Type Designation

    The codes of model HY5W-9L mean: HY = polymer-housed metal-oxide surge arrester; 5 = nominal discharge current 5 kA; W = gapless; 9 = rated voltage of the arrester, 9 kV; L = with disconnector. The HY5W-9L polymer-housed metal-oxide surge arrester has a rated voltage of 9 kV, a continuous operating voltage of not less than 7.65 kV and an 8/20 μs lightning impulse residual voltage of not more than 27 kV, meeting the overvoltage protection requirements of distribution systems at the corresponding voltage level.

    Typical technical parameters

    ModelHY5W-9L
    Rated current (kA)5
    Rated voltage (kV)9
    Continuous operating voltage (kV≥)7.65
    1/4μs Steep-front impulse residual voltage (kV≤)28.5
    8/20μs Lightning impulse residual voltage (kV≤)27
    30/60μs Switching impulse residual voltage (kV≤)23.1
    2000μs Rectangular-wave current carrying capacity (A)100
    4/10μs High-current withstand capability (kA)65

    Disconnector installation diagram

    HY5W-9L disconnector installation diagram

    Time-current characteristic of the disconnector (this model includes a disconnector)

    Current (A)8002002050.50.05
    Operating time (s)0.01-0.020.02-0.050.1-0.20.5~1.020-50200-500

    The letter L after the model designation indicates that a disconnector is included: when an abnormal current occurs in the arrester, the disconnector operates automatically according to the table above, removing the damaged arrester from the system and allowing maintenance personnel to replace it in time.

    Service Conditions

    • Ambient temperature: not higher than +40 ℃ and not lower than -40 ℃;
    • Altitude not higher than 2000 m;
    • Rated frequency: 50 Hz or 60 Hz;
    • The voltage continuously applied to the arrester shall not exceed its continuous operating voltage;
    • Max. wind speed: 35 m/s;
    • Seismic intensity: not greater than degree 7.