"Complies with IEC 62271" is not a specification. The series runs to dozens of parts, and each part covers a different device or assembly. Quoting the wrong one in a tender is a common and expensive mistake, because type-test evidence for one part does not transfer to another.
| Part | What it covers |
|---|---|
| IEC 62271-1 | Common specifications for AC switchgear and controlgear — the definitions, ratings and test philosophy the other parts build on |
| IEC 62271-100 | AC circuit-breakers |
| IEC 62271-102 | AC disconnectors and earthing switches |
| IEC 62271-103 | AC switches (current edition 2023) for rated voltages above 1 kV up to and including 52 kV |
| IEC 62271-105 | AC switch-fuse combinations (current edition 2023) for rated voltages above 1 kV up to and including 52 kV |
| IEC 62271-107 | AC fused circuit-switchers, 1 kV to 52 kV |
| IEC 62271-200 | AC metal-enclosed switchgear and controlgear, 1 kV to 52 kV |
| IEC 62271-201 | AC solid-insulation enclosed switchgear and controlgear, 1 kV to 52 kV |
| IEC 62271-202 | High voltage / low voltage prefabricated substations |
| IEC 60282-1 | High voltage current-limiting fuses — the fuse half of any combination |
The 2023 revisions of IEC 62271-103 and 62271-105 tightened the way combinations are declared and tested. IEC 62271-105 requires the fuses to be fitted with strikers, so that operation of any fuse opens all three poles of the switch, and it explicitly handles the awkward band of fault current between a fuse's minimum melting current and its minimum breaking current. It also excludes combinations requiring dependent manual operation — a small clause with large consequences for anyone specifying an operator-dependent design.